Accueil
Qui sommes-nous
produits
Télécharger
Bibliothèque technique
Contact
Demande de renseignements
Plan du site
Liens
 

Alarme et Câble Audio et électronique

Câble équivalent de Belden

Câbles Coaxiaux

Câbles de contrôle

Câbles Fibres Optiques

Câbles Flexibles

Câble d'instrumentation

Lan Câbles
Câbles d'Energie
Câbles résistants au feu
Câbles Industriels
Railway Câble

Robotique

Rolling Stock câble
Caoutchouc et Câble Crâne
Câble de Sécurité

Câble Téléphonique

Aéroport Câbles

Câbles bus

Cable Glands

Data Cable

Câbles de détection de chaleur
Câbles hautes températures
Autoroute Câbles
Marine, pétrole, gaz et pétrochimie Câbles
Câbles spécial
Spiral Câbles
Câbles thermocouple
Other Cables
     
  indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Câbles Téléphonique

 SR Insulated & LSZH Sheathed Fire Resistant Cables to DIN VDE 0815

JE-H(St)H…Bd FE180 E30        JE-H(St)H…Bd FE180 E30 BMK

Application

The cables are similar in design and application to CW 1600, but with Silicon Rubber Insulation. They are used for the internal wiring of building when the circuit integrity during fire is paramount. The cables are intended for use in fire fighting plants with special ceramized silicon insulation, with and without aluminium foil and LSZH outer sheath

Standards

• EN 50200:2000-02
• EN 50266
• EN 50267
• EN 50268
• BS 6387
• IEC 60331
• DIN VDE 0472-814

 

 

Construction

Conductors
Solid annealed bare or tinned copper sized 0.6/0.8/0.9mm as per class 1 of VDE 0295/IEC 60228

Isolation
Silicon Rubber compound as per DIN VDE 0266

Twisted Pairs
Insulated conductors are twisted into pairs with varying lay length to minimize crosstalk

Elément de câblage
Twisted Pairs

Core Assemblée
The twisted pairs are stranded to the core in layers

Core Wrapping
One or more non hygroscopic polyester tapes are helically or longitudinally laid with an overlap prior to sheathing

Écran
A laminated Aluminium/Polyester tape is placed in contact with solid copper 0.6mm or 0.8mm drain wire

Inner literie (for armoured cables)
PE or LSZH compound.

Armour (for armoured cables)
Either corrugated steel tape armour or galvanized steel wire is applied over an inner polyethylene sheath. For steel tape armour, the 0.15mm thick steel tape is coated with a copolymer and applied with an overlap. For steel wire armour, single layer of galvanized steel wire armour is applied

Gaine
LSZH compound HM2 as per VDE 0207-24

Ripcord
Nylon ripcord may be placed parallel to the cores to facilitate sheath removal

Drain Wire
A solid tinned earth/continuity wire shall be laid longitudinally for screened cables

Type Codes

JE- Fire Alarm Cable H Halogen Free & Zero Halogen
Bd Unit stranding (St) Static Shield of aluminium tape
FE180 Insulation Integrity (950°C 180 minutes) E30 30 minutes Circuit Integrity

 

 

Electrical Properties

Chef d'orchestre Diamètre

mm

0.6

0.8

0.9

Conductor Taille

mm2

0.283

0.5

0.312

Maximum Conductor Resistance @20°C

Ω/km

63

34.6

28.0

Maximum de résistance de boucle @20°C

Ω/km

130

73.2

60

Minimum de résistance d'isolement @500V DC @20°C

MΩ.km

100

100

100

Maximum Moyenne Attenuation @0.8KHz

dB/km

1.7

1.2

0.74

Nominal Mutual Capacitance @0.8KHz

nF/km

120

120

120

Capacité maximale Unbalance K1 @0.8KHz pair-to-pair

pF/100m

200

200

200

Working Voltage

V

225

225

225

Epaisseur d'isolation nominale

mm

0.3

0.4

0.45

Insulated Conductor Diamètre nominale

mm

1.2

1.6

1.7

Mechanical and Thermal Properties

Temperature range during operation (fixed state): -30°C – +70°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 7.5 x Overall Diameter (unarmoured cable);15 x Overall Diameter (armoured cables)

Fire Hazard Performance

1) Minimum Smoke Emission IEC 61034, EN 50268 ( New: EN 61034), VDE 0482-268 ( New: VDE 0482-1034)
These standards specify a method to measure the generation of smoke from cables during fire. The result is expressed as percentage of light transmitted. Usually, the smoke density shall not be less than 60%.
2) Halogen Free  IEC 60754-1, EN 50267-2-1
These standards specify a method for determination of the amount of halogen acid gas, evolved during combustion of compound. The hydrochloric acid yield should be less than 0.5%.
3) Non corrosive gases IEC 60754-2, EN 50267-2-2, VDE 0482-267
These  standards  specify  a  method  for  determination  of  acidity  of  gas  evolved  during combustion of cables by measuring PH and conductivity. The specimen is deemed to pass this test if the pH value is less than 4.3 when related to 1 litre of water and conductivity is less than 10 μs/min.
4) Reduced Fire Propagation IEC 60332-3C, EN 50266-2-4, VDE 0482-266-2-4
These standards specify a method for flame propagation test for bunched cables.
5) Flame Retardancy IEC 60332-1, VDE 0482-265-2-1
These standards specify a method for flame propagation test for single core cables.
6) Temperature Index BS EN ISO 4589-3, BS 2782 Part 1
These standards specify a method for measuring the temperature Index of materials. The temperature index shall be equal or greater than 280ºC.
7) Oxygen Index BS EN ISO 4589-2, BS 2863
These standards specify a test for measuring the minimum oxygen concentration to support candle like combustion of plastics. The oxygen index shall not be less than 30%.

 

 

 

 

 

 

 

 

 

 

 

 

 

Colour Code

Quad colour in each bundle:
Pair 1: Blue-Red         Pair 2: Green-Yellow         Pair 3: Green-Brown         Pair 4: White-Black
The individual bundles are identified by a numbered helix.

Dimensions And Weight

VDE CODE: JE-H(St)H…x2x0.8 Bd FE180 E30

Cable Code Nombre de paires Epaisseur d'isolation nominale
mm
Gaine Epaisseur nominale
mm
Diamètre nominal
mm
Poids nominal
kg/km
0.8mm Conductor, 1.6mm Insulated Wire

TP815JE-H(St)H-Bd-FE180-E30-1P08

1

0.4

1.0

6.0

46

TP815JE-H(St)H-Bd-FE180-E30-2P08

2

0.4

1.0

6.6

61

TP815JE-H(St)H-Bd-FE180-E30-4P08

4

0.4

1.0

8.8

104

TP815JE-H(St)H-Bd-FE180-E30-6P08

6

0.4

1.0

10.8

160

TP815JE-H(St)H-Bd-FE180-E30-8P08

8

0.4

1.0

12.8

218

TP815JE-H(St)H-Bd-FE180-E30-10P08

10

0.4

1.2

13.1

220

TP815JE-H(St)H-Bd-FE180-E30-12P08

12

0.4

1.2

13.5

235

TP815JE-H(St)H-Bd-FE180-E30-16P08

16

0.4

1.2

14.7

297

TP815JE-H(St)H-Bd-FE180-E30-20P08

20

0.4

1.2

16.1

367

TP815JE-H(St)H-Bd-FE180-E30-24P08

24

0.4

1.4

18.1

440

TP815JE-H(St)H-Bd-FE180-E30-30P08

30

0.4

1.4

20.1

645

TP815JE-H(St)H-Bd-FE180-E30-32P08

32

0.4

1.4

20.6

645

TP815JE-H(St)H-Bd-FE180-E30-40P08

40

0.4

1.4

22.5

656

TP815JE-H(St)H-Bd-FE180-E30-50P08

50

0.4

1.6

24.3

840

VDE CODE: JE-H(St)H(SWA)H…x2x0.6/0.8/0.9 Bd FE180 E30

Cable Code Nombre de paires Epaisseur d'isolation nominale
mm
Nominal Literie/
Gaine Epaisseur
mm
Diamètre nominal
mm
Poids nominal
kg/km
0.6mm Conductor,1.2mm Insulated Wire

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-2P06

2

0.3

1.0/1.8

12.1

305

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-3P06

3

0.3

1.0/1.8

12.6

325

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-6P06

6

0.3

1.0/1.8

13.2

380

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-8P06

8

0.3

1.0/1.8

14.6

415

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-10P06

10

0.3

1.0/1.8

16.5

450

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-12P06

12

0.3

1.0/1.8

17.0

500

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-20P06

20

0.3

1.0/1.8

20.5

580

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-25P06

25

0.3

1.0/1.8

21.5

940

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-30P06

30

0.3

1.0/1.8

22.5

1300

0.8mm Conductor, 1.6mm Insulated Wire

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-2P08

2

0.4

1.0/1.8

14.0

415

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-3P08

3

0.4

1.0/1.8

14.0

425

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-6P08

6

0.4

1.0/1.8

15.0

485

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-8P08

8

0.4

1.0/1.8

17.5

520

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-10P08

10

0.4

1.2/1.8

19.0

540

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-12P08

12

0.4

1.2/1.8

20.5

600

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-20P08

20

0.4

1.4/1.8

24.5

1050

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-25P08

25

0.4

1.4/1.8

27.0

1250

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-30P08

30

0.4

1.4/1.8

28.5

1450

0.9mm Conductor, 1.7mm Insulated Wire

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-10P09

10

0.45

1.2/1.8

19.7

600

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-15P09

15

0.45

1.2/1.8

23.0

1020

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-20P09

20

0.45

1.4/1.8

25.3

1160

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-25P09

25

0.45

1.4/1.8

27.3

1330

TP815JE-H(St)H(SWA)H-Bd-FE180-E30-30P09

30

0.45

1.4/1.8

29.3

1520